Realistic experimental heat transfer characteristics of radiant floor heating using sidewalls as heat sinks


AÇIKGÖZ Ö., Karakoyun Y., YUMURTACI Z., Dukhan N., DALKILIÇ A. S.

Energy and Buildings, cilt.183, ss.515-526, 2019 (SCI-Expanded) identifier

  • Yayın Türü: Makale / Tam Makale
  • Cilt numarası: 183
  • Basım Tarihi: 2019
  • Doi Numarası: 10.1016/j.enbuild.2018.11.022
  • Dergi Adı: Energy and Buildings
  • Derginin Tarandığı İndeksler: Science Citation Index Expanded (SCI-EXPANDED), Scopus
  • Sayfa Sayıları: ss.515-526
  • Anahtar Kelimeler: Enclosure, Energy saving, Floor heating, Natural convection, Radiant heating
  • Van Yüzüncü Yıl Üniversitesi Adresli: Hayır

Özet

Apart from most of the relevant literature, case studies are conducted by generating a number of configurations using sidewalls as heat sinks to simulate winter conditions. These configurations correspond to distinct heat loss rates and means from a living environment, heated by an underfloor heating system. In this study, heat transfer characteristics of an underfloor heating system in a test chamber have been experimentally determined, while chilled water flows through circuits in sidewalls arranged at four different configurations. Simultaneously, supply water temperatures ranging from 30 °C to 45 °C, and a flow rate of 0.09 kg/s are applied. As a result, when the supply water temperature is 35 °C, with increasing number of cooled sidewalls, at configuration 2, 3, and 4 as increasing heat loss sources, total heat fluxes from the floor are found 66.36 W/m2, 81.79 W/m2, and 85.19 W/m2, respectively. Correlations for the convective heat transfer coefficient and total heat flux are derived and average error rates of ± 11% and ± 4.5% are obtained, as 87.5% and 94% of measured data remain in ± 30% and ± 10% error bands considering the derived empirical correlations, respectively. Measured and calculated data are given for other researchers to validate their models.